وزن | 1350 کیلوگرم |
---|
ابعاد | 136X235X114 |
---|
وزن تقریبی | 1350 گرم |
---|
پیوستگی | (Accuracy: ±0.1Ω (0 – 0.19Ω) | ±2%rdg+8dgt (0.2 – 2000Ω, (Open circuit voltage (DC): 5V±20% (*1, (Range: 20/200/2000Ω (Auto-ranging, Short circuit current: Greater than 200mA |
---|
مقاومت عایقی | (Accuracy: ±2%rdg+6dgt (0 – 19.99MΩ) / ±5%rdg+6dgt (20 – 200MΩ) | ±2%rdg+6dgt (0 – 199.9MΩ) / ±5%rdg+6dgt (200 – 2000MΩ, (Range : 20/200MΩ (Auto-ranging) |20/200/2000MΩ (Auto-ranging, Open circuit voltage (DC): 250V+25% -0% | 500V+25% -0% | 1000V+20% -0%, Rated current: 1mA or greater @ 250kΩ | 1mA or greater @ 500kΩ | 1mA or greater @ 1MΩ |
---|
امپدانس لوپ | (Accuracy for L-N/L-L: ±3%rdg+4dgt (*3) | ±3%rdg+8dgt(*4, (Accuracy for L-PE: ±3%rdg+4dgt(*3) | ±3%rdg+8dgt(*4, (Accuracy for L-PE(ATT): ±3%rdg+6dgt (*3) | ±3%rdg+8dgt(*4, (Range for L-PE (ATT):20/200/2000Ω (Auto-ranging) (L-N < 20Ω, (Range for L-PE: 20/200/2000Ω (Auto-ranging, for L-N/ L-L: 20Ω: 6A/20ms, for L-PE (ATT): L-N: 6A/60ms | N-PE: 10mA/approx. 5s, Function: L-PE | L-PE (ATT) | L-N / L-L, Nominal Test Current at 0Ω External Loop: Magnitude/ Duration for L-PE: 20Ω: 6A/20ms | 200Ω: 2A/20ms | 2000Ω: 15mA/500ms, Range for L-N/L-L: 20Ω, Rated Voltage for L-N / L-L: L-N: 100 – 300V | L-L: 300 – 500V 50/60Hz, Rated Voltage for L-PE & L-PE(ATT): 100 – 260V 50/60Hz |
---|
PSC (L-N / L-L) / PFC (L-PE) | (Function: PSC | PFC | PFC (ATT, Accuracy: PSC / PFC accuracy is derived from measured loop impedance specification and measured voltage specification, Nominal Test Current at 0Ω External Loop: Magnitude/ Duration (*5) for PFC (ATT): L-N: 6A/60ms | N-PE: 10mA/approx. 5s, Nominal Test Current at 0Ω External Loop: Magnitude/ Duration (*5) for PFC: 6A/20ms 2A/20ms 15mA/500ms, Nominal Test Current at 0Ω External Loop: Magnitude/ Duration (*5) for PSC: 6A/20ms, Range: 2000A/20kA Auto-Ranging, Rated Voltage for PFC: 100 – 260V | 50/60Hz, Rated Voltage for PSC: 100 – 500V | 50/60Hz |
---|
(RCD (Uc | _100V, (Test current: ≤ 1/2IΔn (max150mA, Accuracy: +5% – +15%rdg, ±8dgt, Function: UC, Rated Voltage: 230V+10% – 15% | 50/60Hz |
---|
RCD | [Rated Voltage: 230V+10%-15% [50/60Hz, Accuracy for Ramp: AC Type: ±4% | A Type: ±10%, Accuracy for X1 & X5: AC Type: +2% – +8% | A Type: 0% – +10%, Accuracy for X1/2: AC Type: -8% – -2% | A Type: -10% – 0%, Accuracy: Trip time: ±1%rdg+3dgt, Function: X1/2 | X1 | X5 | Ramp, Trip current Duration for Ramp: Goes up by 10% from 20% to 110% G:300ms/ S:500ms X10 times, Trip current Duration for X1: G: 550ms S: 1000ms, Trip current Duration for X1/2: 2000ms, Trip current Duration for X5: 410ms, Trip current setting for Ramp: 10/30/ 100/300/ 500mA, Trip current setting for X1/2 & X1:10/30/100/300/ 500/1000mA, Trip current setting for X5: 10/30/ 100mA |
---|
Earth | Accuracy: 20Ω: ±3%rdg+0.1Ω | 200/2000Ω: ±3%rdg+3dgt (Auxiliary earth resistance 100±5%), Range: 20/200/2000Ω Auto-Ranging |
---|
Phase Rotation | [Rated Voltage: 50-500V [50/60Hz, Remarks: Correct phase sequence: are displayed "1.2.3" and cycle mark | Reversed phase sequence: are displayed "3.2.1" and cycle mark |
---|
Volts | Accuracy for Frequency: ±0.5%rdg+2dgt, Accuracy for Volts: ±2%rdg+4dgt, Function: Volts| Frequency, Measuring range for Frequency: 45 – 65Hz, Measuring range for Volts: 25 – 500V, Rated Voltage : 25 – 500V | 45 – 65Hz |
---|
منبع تغذیه | LR6 X 8 |
---|
استاندارد های مناسب | (IEC 61557-1, 2, 3, 4, 5, 6, 7, 10 | IEC 60529 (IP40) | IEC 61326 (EMC, IEC 61010-1 CAT III 300V (500V L to L) Pollution degree 2 | IEC 61010-031, |
---|
تجهیزات و اقلام همراه | ((8212-USB (USB adaptor with KEW Report (Software, (7188A (Distribution board fuse test lead set, (7196A (Test leads with remote control switch, (7218A (Power cord [EU]) (*6, (7228A (Earth resistance test leads, 8032 (Auxiliary earth spikes), 9121 (Shoulder strap), 9142 (Carrying case), Cord case, Buckle, Battery, Instruction manual |
---|
نقد و بررسی وجود ندارد.